4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472
URL: www.iscenclosurecooling.com ● Email: iscinfo@iscsales.com
SP-ENG-210-100-09 Rev 1.6 8 | P a g e
CAUTION
If mounting the air conditioner to the enclosure door, confirm with the enclosure manufacturer that the
door’s hinges will support the air conditioner’s added weight (see equipment specifications). Insure
that when the door is fully open that the enclosure will not topple over due to the off-center load.
Unit Specifications
The following tables provide electrical and refrigeration specifications for the RZ-01 Series Air
Conditioners.
RZ-01A Series
Nominal Capacity Rating: 1,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 57lbs (120/230VAC)
Operating
Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Fuse Selection
(Amps)
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
12 Amp Class
CC, CCMR
Time Delay *
7 Amp Class
CC, CCMR
Time Delay *
* Time-delay Fuses with the following electrical characteristics are recommended. Fast -acting fuses
are not recommended.
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.